External sensor control

When using this control strategy, the solar shading is being controlled according to the light intensity on the facade. When the lighting level, measured on the facade where the window is located, exceeds the value of Shade Close (lux), the shading is being closed. The solar shading will remain closed until the lighting level on the facade drops below the value of Shade Open (lux).

Dialog for definition of solar shading control by an external sensor - SensorCtrl.
Dialog for definition of solar shading control by an external sensor - SensorCtrl.



Data in the dialog defining the control type SensorCtrl.

Parameter Description Variants / interval, unit Standard value
Shading Coeff. Solar shading factor for the shading device, when it is being closed completely. This value overrides an eventual value given for the system SolarShading. 0–1.0 0.5
Shade Close Limit for lighting level on the facade, over which the solar shading is being closed. 3 000–80 000 lux 20 000 lux
Shade Open Limit for lighting level on the facade, below which the shading is being opened. 2 000–20 000 lux 10 000 lux
Sf4 shading Solar light factor for the window with the solar shading closed. 0–0.5 0.05

results matching ""

    No results matching ""