Recirculation

Recirculation of ventilation air happens according to the pseudo-code shown below.


Principle diagram for ventilation systems with recirculation of air
Principle diagram for ventilation systems with recirculation of air.

The numbers in the figure refers to the general description of the state of the air in ventilation the system and building. Recirculation (Return air) can control the conditions in the thermal zone by:

  • changing the share of return air (the share between the air flows 5a/11)

  • change the (total) inlet air flow (11)

  • humidifier (9 → 10)

  • de-humidifier (cooling coil) (6 → 7)

Input to ventilation systems

In the present general data, the existing fan equals fan 1: supply and 2: exhaust. Two additional fans must be added: 3: return and 4: intake. Normally the current return fan will be placed as fan 2 in the figure above.

It should be considered if MinHeatRec and MaxCoolRec should be moved to the control tab later on (in some cases they can be considered being control parameters).

Input to recirculation: ReturnairCtrl

Parameter Unit Meaning
MinSupplyRatio 0–1,0 Lower value for share of nominal inlet air flow. The proportion between SupplyAir and Exhaust is kept constant when Supply is being changed.
MinReturnRatio 0–1,0 Lower limit for share of recirculated air compared to Supply
MaxReturnRatio 0–1,0 Upper limit for share of recirculated air compared to Supply
SetP CO₂ ppm Upper limit for CO₂ content in zone air
SetPHumid % Lower limit for relative humidity in zone air
SetPDehumid % Upper limit for relative humidity in zone air
MinInletTemp °C Lower limit for inlet air temperature
MaxInletTemp °C Upper limit for inlet air temperature
SetPTemp °C Desired set-point for operative temperature in the thermal zone

Start conditions for first time-step

Parameter Value in first time-step Explanation
SupplyRatio MinSupplyRatio The lowest possible air flow is blown into the thermal zone
ReturnRatio MaxReturnRatio The highest share (compared to Supply) of recirculation is being used
InletTemp ZoneAirTemp The zone air temperature in the previous time-step

Start conditions for next time-steps

Parameter Value in next time-step Explanation
SupplyRatio SupplyRatio Value in previous time-step
ReturnRatio ReturnRatio Value in previous time-step
InletTemp ZoneAirTemp Zone air temperature in previous time-step

Control priority

  1. CO2

  2. Moisture

  3. Temperature

Control of CO2

value in the zone (4) below SetP CO2: no control

value in the zone (4) above SetP CO2:

control:

  1. if ZoneAirCO2 > OutdoorAir CO2: reduction of ReturnRatio

  2. when/if ReturnRatio=MinReturnRatio: increase of SupplyRatio

Intern parameter: calculate MinOutdoorAir to obtain SetP CO2 (minimum outdoor air-flow to keep the CO2 level below CO2 SetPoint).

Control of moisture

Conversion of SetPHumid and SetPDehumid to values of relative humidity at temperature SetPTemp. If the value in the zone (4) is above SetPHumid and below SetPDehumid: no control

value in the zone (4) below SetPHumid:

control

  1. (increase of ReturnRatio - can hardly be a situation that occurs)

  2. humidification via Humidifier (9 → 10) with a check that the state of the indoor air do not go above the saturation curve for air state 9

  3. if the saturation curve is reached: increase of SupplyRatio (- calculate how much!)

  4. humidification via Humidifier (9 → 10) with a check that the state of the indoor air do not go above the saturation curve for air state 9

value in zone (4) above SetPDehumid:

control

  1. if ZoneAirHum > OutdoorAirHum: reduction of ReturnRatio

  2. when/if ReturnRatio = MinReturnRatio: increase of SupplyRatio

  3. when/if SupplyRatio = 1: start cooling coil for de-humidification (6 → 7)

Control of temperature

Value in zone (4) is below (ZoneAirTemp - DeltaT):

Control

  1. start heating coil until ZoneAirTemp = SetPTemp (7 → 8)

  2. start radiator until ZoneAirTemp = SetPTemp

Value in zone (4) is above (ZoneAirTemp + DeltaT):

Control

  1. if ClCoil > MaxCoolPower (negative): increase cooling power (6 → 7)

  2. if the zone indoor air humidity goes below SetPHumid: start humidifier (9 → 10)